Shop Detail
Tripp Lite, UPS, SmartOnline 3000VA, 2700W, 2U, 100/110/120/127V, 5-15R, 5-15/20R, USB, DB9
  • Cost: $2218.95
  • Quantity: 9
  • Free Shipping
  • Views:
  • Sold and Shipped By: Aztek Computers
Tripp Lite SmartOnline 120V 3kVA 2.7kW Double-Conversion 2U Rack/Tower UPS
OUTPUT
Output Volt Amp Capacity (VA):3000
Output kVA Capacity (kVA):3
Output Watt Capacity (Watts):2500
Output kW Capacity (kW):2.5
Power Factor:0.83
Crest Factor:3:1
Nominal Output Voltage(s) Supported:100V 110V 115V 120V 127V
Nominal Voltage Details:120V default Frequency Compatibility:50 / 60 Hz
Frequency Compatibility Details:Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start. Frequency conversion from 60 to 50 Hz -or- 50 to 60 Hz supported. Output capacity de-rates by 25% during frequency conversion operation. Output Voltage Regulation (Line Mode):+/- 2%
Output Voltage Regulation (Economy Line Mode):-12%, + 10%
Output Voltage Regulation (Battery Mode):+/- 2%
Output Receptacles:(6) 5-15/20R (1) L5-30R
Load Management Receptacles:Two switchable three-outlet load banks Output Circuit Breakers:20A (x2) - each breaker protects 3 5-15/20R outlets, L5-30R outlet is un-breakered
Output AC Waveform (AC Mode):Pure Sine wave
Output AC Waveform (Battery Mode):Pure Sine wave INPUT
Rated input current (Maximum Load):24A
Nominal Input Voltage(s) Supported:100V AC 110V AC 115V AC 120V AC 127V AC
UPS Input Connection Type:L5-30P
Recommended Electrical Service:30A 120V
Input Cord Length (ft.):10
Input Cord Length (m):3
Input Phase:Single-Phase BATTERY
Full Load Runtime (min.):6 min. (2500w)
Half Load Runtime (min.):15 min. (1250w)
Expandable Battery Runtime:Supports extended runtime with optional external battery packs External Battery Pack Compatibility:BP72V15-2U (limit 1) BP72V28RT-3U (multi-pack compatible) BP72V18-2US (multi-pack compatible)
DC System Voltage (VDC):72
Battery Recharge Rate (Included Batteries):Less than 4.8 hours from 10% to 90% (typical, full load discharge) Internal UPS Replacement Battery Cartridge:RBC96-2U
Battery Access:Front panel battery access door
Battery Replacement Description:Hot-swappable, user replaceable batteries
Expandable Runtime:Yes VOLTAGE REGULATION
Voltage Regulation Description:Online, double-conversion power conditioning
Overvoltage Correction:2% output voltage regulation during overvoltages to 144
Undervoltage Correction:2% output voltage regulation during undervoltages to 80
Severe Undervoltage Correction:2% output voltage regulation during undervoltages to 70V (under 66% load only) or 60V (under 33% load only) USER INTERFACE, ALERTS and CONTROLS
Switches:2 Switches control off/on power status and alarm-cancel/self-test operation Alarm Cancel Operation:Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm:Audible alarm indicates power failure, low battery, overload, replace battery and EPO operation LED Indicators:14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information 4-LED meter displays load and battery charge levels LED panel rotates for viewing in rack/tower formats SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating:504 joules
EMI / RFI AC Noise Suppression:Yes
AC Suppression Response Time:Instantaneous COMMUNICATIONS
Communications Interface:USB (HID enabled) DB9 Serial Contact closure EPO (emergency power off) Slot for SNMP/Web interface Network Monitoring Port Description:Supports detailed monitoring of UPS and site power conditions DB9 port supports RS232 and contact closure communications PowerAlert Software:Included
Communications Cable:USB and DB9 cabling included
WatchDog Compatibility:Supports Watchdog application, OS and hard-reboot restart options for remote applications LINE / BATTERY TRANSFER:
Transfer Time:No transfer time (0 ms.) in online, double-conversion mode
Low Voltage Transfer to Battery Power (Setpoint):80V (100% load), 70V (66% load), 60V (33% load)
High Voltage Transfer to Battery Power (Setpoint):144 SPECIAL FEATURES:
Cold Start (Startup in Battery Mode During a Power Failure):Cold-start operation supported
High Availability UPS Features:Automatic inverter bypass Hot swappable batteries Green Energy-Saving Features:High efficiency economy mode operation Individually controllable load banks Schedulable daily hours of economy mode operation CERTIFICATIONS
UPS Certifications:Tested to UL1778 (USA) Tested to CSA (Canada) Tested to NOM (Mexico) Meets FCC Part 15 Category A (EMI)